Serial Number High (Upper display).
Range: 0 to 9999. Read only.
Serial Number Low (Lower display).
Range: 0 to 9999. Read only.
Control Setpoint (Prompt Setpoint).
Range: from spll to spkl.
Setpoint Low limit.
Range: minimum value depends on the input type selected
in type (see Table 1) to spkl.
Setpoint High limit.
Range: minimum value is spll and maximum depends on
the input type selected in type (see Table 1).
Offset value of PV(Process value).
Range: from spll to spkl
.
PV decimal point position
Range: 0 to 3
00.000; 100.00; 2000.0; 30000
Alarm 1 Setpoint.
Range: From spll to spkl for non differential; and
spkl - spll for differential alarm.
Alarm 2 Setpoint. Range: same as in spa1.
Alarm 3 Setpoint. Range: same as in spa1.
Alarm 4 Setpoint. Range: same as in spa1.
Alarm 1 Function. Range: 0 to 8
0 off
1ierr
2 T.END
3 rs
4 lo
5 ki
6 dif
7 difl;
8 difk;
Alarm 1 Hysteresis. Range: 0 to 9999 (0.00 to 99.99%)
Alarm 2 Hysteresis. Range: same as in kya1.
Alarm 3 Hysteresis. Range: same as in kya1.
Alarm 4 Hysteresis. Range: same as in kya1.
PV input type:
0 = J
1 = K
2 = T
3 = N
4 = R
5 = S
6 = B
7 = E
8 = Pt100
9 = 0-20 mA
10 = 4-20 mA
11 = 0-50 mV
12 = 0-5 V
13 = 0-10 V
Communication slave address. Range: 1 to 247
Communication Baud-Rate:
01200;12400;24800;39600; 419200;
538400; 657600; 7115200;
Control Mode. Range: 0manual; 1automatic.
Enable control. Range: 0no; 1yes.
Control action. Range: 0direct; 1reverse.
Auto tune enable:
0= off;1= Fast; 2= Full; 3= Self; 4= rSLF; 5= tGHt;
Alarm power-up inhibit. Range: 0no; 1yes.
Key press remote action. Range: 0 to 9
1: tecla P
2: tecla
4: tecla
8: tecla B
9: teclas P e B
Alarm 1 Time 1. Range: 0 to 6500s.
Refer to operation manual for more details.
Alarm 1 Time 2 (in seconds).
Range: same as in a1t1.
Alarm 2 Time 1 (in seconds).
Range: same as in a1t1.
Alarm 2 Time 2 (in seconds).
Range: same as in a1t1.
Soft-Start time (in seconds).
Range: 0 to 9999
Temperature unit. Range: 0 to 1.
0C; 1F.
Bias. Range: -100 to +100%.
Ramp and Soak segment being executed (read only).
Range: 0 to 9.
Ramp and Soak segment to be viewed or edited.
Range: 1 to 20.
Ramp and Soak segment to be executed.
Range: 0 to 20.
Indicates the remaining time of the Ramp and Soak
segment.
Square root of a linear input.
Range: 0->Disable;1->Enable.
Enter the low input value currently applied in the PV input
for calibration purposes.
Enter the high input value currently applied in the PV input
for calibration purposes.
Enter the low input value currently applied in the remote
setpoint input for calibration purposes.
Enter the high input value currently applied in the remote
setpoint input for calibration purposes.
Enables the top display blinking as a function of the
selected alarm:
0-> Disable
1-> Enable to alarm 1
2-> Enable to alarm 2
3-> Enable to alarm 1 and 2
Restores original default calibration.
Range: 0 to 1; 0-> do not restore; 1-> restore calibration