Novus DigiRail- DigiRail-4C Manual de usuario Pagina 4

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 5
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 3
DigiRail-4C
NOVUS AUTOMATION 4/5
Address Description SuperView Mnemonic Minimum Maximum R/W
70
Counted pulses in the last interval for input 4 - least
significant word
PulseRate4L 0 65535 R
71
Maximum of pulses counted on time interval for input
1 - most significant word
PeakPulse1H 0 65535 R
72
Maximum of pulses counted on time interval for input
1 - least significant word
PeakPulse1L 0 65535 R
73
Maximum of pulses counted on time interval for input
2 - most significant word
PeakPulse2H 0 65535 R
74
Maximum of pulses counted on time interval for input
2 - least significant word
PeakPulse2L 0 65535 R
75
Maximum of pulses counted on time interval for input
3 - most significant word
PeakPulse3H 0 65535 R
76
Maximum of pulses counted on time interval for input
3 - least significant word
PeakPulse3L 0 65535 R
77
Maximum of pulses counted on time interval for input
4 - most significant word
PeakPulse4H 0 65535 R
78
Maximum of pulses counted on time interval for input
4 - least significant word
PeakPulse4L 0 65535 R
79-84 Reserved
-
0 0 R
DETAILS OF SOME REGISTERS
REGISTER 2 – BAUD RATE
Code of speed used in Modbus communication.
Code Baud rate
0 1.200
1 2.400
2 4.800
3 9.600
4 19.200
5 38.400
6 57.600
7 115.200
REGISTER 3 – MODBUS ADDRESS
Address of the device in the Modbus network. Valid values: from 1 to 247. We recommend using the lower addresses for
the equipment.
REGISTER 4 – PARITY
Code of the parity used in Modbus communication.
Code Parity
0 No parity
1 Odd
2 Even
REGISTER 5 – FIRMWARE VERSION
Indicates the firmware version of the equipment, according to the examples below:
If the version is "1.00", the value "100" will be read. If the version is "2.04", the value "204" will be read.
REGISTER 6 – DIAGNOSTIC STATE TIMER
Internally used by the DigiConfig software.
REGISTER 7 – STATE OF THE DIGITAL INPUTS
Bit at 0: Input deactivated
Bit at 1: Input activated
Bit 15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Entry - - - - - - -
-
-
-
-
-