PROGRAM LEVEL
Program
Tolerance
Maximum admitted deviation of PV with respect to SP.
If exceeded, the program execution is suspended (the
internal timer freezes) until the deviation be returns
back within the defined tolerance.
The value 0 (zero) disables the function.
Program SP
Program SP’s, 0 to 9: Group of 10 values of SP that
define the Ramp and Soak profile segments.
Program Time
Time intervals of the program segments. It defines
the duration in minutes, of each of the 9 program
segments. Configurable between 0 and 9999
minutes.
Program
event
Program Segment Alarm (Event Alarm). Parameters
that define the alarm must be activated during the
execution of a certain program segment:
OFF Do not activate alarm in this segment.
A1 Activate alarm 1 when program reaches
this segment.
A2 Activate alarm 2 when program reaches
this segment.
A1A2 Activate alarms 1 and 2 when program
reaches this segment.
The alarms chosen must have its function configured
as “
”.
Repeat
Program
It determines the number of times the program must
be REPEATED, besides the initial execution.
Configurable between 0 and 9999 times. After the
last execution, all controller outputs are turned off
(RUN = OFF).
INPUT LEVEL
tYPE
INPUT TYPE: Selects the input signal type to be
connected to the process variable input. Refer to
Table 1 for the available options.
This must be the first parameter to be
configured.
Decimal Point
DECIMAL POINT.
Defines the decimal point
position.
unit
UNIT: Defines the indication unit in Celsius or
Fahrenheit
Degrees Celsius (°C);
Degrees Fahrenheit (°F);
ACtion
CONTROL ACTION:
Reverse action. Generally used for
heating.
Direct action. Generally used for
cooling.
OUTA, OUTB, OUTC and OUTD function:
Output not used
Output defined as control output
Output defined as alarm output 1
Output defined as alarm output 2
Output defined as control output 0-20
mA (only for OUTD)
Output defined as control output 4-20
mA (only for OUTD)
SP Low Limit
SETPOINT LOW LIMIT: Selects minimum
adjustment for parameters relative to the SP (
,
,
).
SP High Limit
SETPOINT HIGH LIMIT: Selects maximum
adjustment for parameters relative to the SP (
,
,
).
OFFSet
OFFSET FOR PV: Parameter that allows to add a
value to PV to generate an indication displacement.
Alarm Function
ALARM FUNCTION 1 AND 2: See Table 4 for
description of functions and code to be
programmed in these screens.
Alarm
HYsteresis
ALARM HYSTERESIS 1 AND 2: Defines the
difference between the measured value when the
alarm is activated and the value that is deactivated.
Alarm
Blocking
Initial Alarm block:
Enables initial block
Does not enable initial block
Program Type
Type of program to be adopted by controller:
Does not adopt any type of program
Adopts ramp to level function
Adopts complete Ramp and Level
program.
CALIBRATION LEVEL
All types of input and output are calibrated at the factory. If recalibration
is required, it must be performed by a specialist. If this cycle is
accessed accidentally, pass through all parameters without making
changes to their values.
Password. Input of the Access Password.
This parameter is presented before the protected
cycles. See item Protection of Configuration.
Input Low Calibration.
corresponding to the low scale signal applied to the
analog input.
Input High Calibration.
corresponding to the full scale signal applied to the
analog input.
Output Low Calibration. Enter of the value
measured at the analog output.
Output High Calibration. Enter of the value
measured at the analog output.
Restore. Restores the factory calibration for all input,
analog output and remote SP, disregarding
modifications carried out by the user.
Cold Junction. Adjusts the of cold junction
temperature value.
Password. Allows defining a new access password,
always different from zero.
Protection. Sets up the Level of Protection. See
Table 2.
TYPE OF ADOPTED PROGRAM
Two forms of program execution are available in the controller. The
Program Type (
) parameter allows user to choose between
Ramp to Level (
) and a complete Ramp and Level program (
).
User can also choose to not execute any type of program (
).
PROGRAMS OF RAMP AND SOAK
Available when the
option in the
parameter is selected.
The controller allows the process temperature to vary gradually from an
initial value until a specified final value, determining a Ramp-like behavior.
The initial value of the Ramp will always be the process initial
temperature (PV). The final value will always be the value defined in SP.
User determines the increase (or decrease) speed of the ramp in the
“
” parameter, which defines a temperature variation rate in degrees
per minute. In order to disable the Ramp function, program the value 0.0.
When the SP value is reached, the controller starts to control the
process in SP (level) by an interval of time or indefinitely.
The
parameter, adjustable between 0 and 9999 minutes,
determines the level duration. At the end of the level, the control is