
Controller N1200
NOVUS AUTOMATION 3 / 13
Using the Alarm 1 as example.
•
– Alarm of Maximum Differential Value
Triggers when the value of PV is above the defined point by:
(SP + SPA1)
Using the Alarm 1 as example.
SCREEN TYPE ACTUATION
Inoperative Output is not used as alarm.
Open sensor
(input Error)
Activated when the input signal of PV is
interrupted, out of the range limits or Pt100
in short-circuit.
r
Soak)
Activated in a specific segment of program.
(resistance fail
Signals a failure in the heating element.
(Low)
(High)
Differential
(diFerential)
Positive SPAn Negative SPAn
Minimum
Differential
(diFerential
Low)
Positive SPAn Negative SPAn
Maximum
differential
(diFerential
High)
Positive SPAn Negative SPAn
Table 3 – Alarm Functions
Where SPAn refers to Setpoints of Alarm “
”, “
”,
“
” and “
”.
ALARM TIMER MODES
The controller alarms can be configured to perform 3 timer modes:
• One pulse with defined duration;
• Delayed activation;
• Repetitive pulses;
The illustrations in Table 4 show the behavior of the alarm output for
various combinations of times t1 and t2. The timer functions can be
configured in parameters
,
,
,
,
,
,
and
.
OPERATION
T 1 T 2 ACTION
Normal
Operation
0 0
Activation for
1 to 6500 s
0
delay
0 1 to 6500 s
Intermittent
Activation
1 to 6500 s
1 to 6500 s
Table 4 – Temporization Functions for the Alarms
The LEDs associated to the alarms will light when the alarm
condition is recognized, not following the actual state of the output,
which may be temporarily OFF because of the temporization.
INITIAL BLOCKING OF ALARM
The initial blocking option inhibits the alarm from being recognized if
an alarm condition is present when the controller is first energized (or
after a transition from run YES NO). The alarm will be enabled
only after the occurrence of a non-alarm condition followed by a new
occurrence for the alarm.
The initial blocking is useful, for instance, when one of the alarms is
configured as a minimum value alarm, causing the activation of the
alarm soon upon the process start-up, an occurrence that may be
undesirable.
The initial blocking is disabled for the sensor break alarm function.
EXTRACTION OF THE SQUARE ROOT
With this feature enabled the controller uses for display and control a
value that corresponds to the square root of the applied input signal.
Available only for the inputs belonging to the group of linear analogic
signals: 0-20 mA, 4-20 mA, 0-50 mV, 0-5 V and 0-10 V.
ANALOG RETRANSMISSION OF PV AND SP
The analog output, when not used for control purposes, is available
for retransmitting the PV and SP values in 0-20 or 4-20 mA. This
analog output is electrically isolated from other inputs and outputs.
The analog output signal is scalable, with the output range defined by
the values programmed in the parameters “
” and “
”.
To obtain a voltage output, the user must install a resistor shunt (550
Ω max.) to the current output terminals (terminals 7 and 8). The
actual resistor value depends on the desired output voltage span.
SOFT-START
The soft-start feature avoids abrupt variations in the power delivered
to the load regardless of the system power demand. .
This is accomplished by defining a limiting ramp for the control output.
The output is allowed to reach maximum value (100 %) only after the
time programmed in the soft-start parameter has elapsed. The Soft-
start function is generally used in processes that require slow start-up,
where the instantaneous application of 100 % of the available power to
the load may cause damages to parts of the system.
In order to disable this function, the soft-start parameter must be
configured with 0 (zero).
REMOTE SETPOINT
The controller can have its Setpoint value defined by an analog,
remotely generated signal. This feature is enabled through the
channels I/O3, I/O4 or I/O5 when configured as digital inputs and
configured with the function
(Remote SP selection) or through
the parameter
. The remote setpoint input accepts the signals
0-20 mA, 4-20 mA, 0-5 V and 0-10 V.
For the signals of 0-20 and 4-20 mA, a shunt resistor of 100
is
required between terminals 9 and 10, as shown in Figure 4c.
CONTROL MODE
The controller can operate in two different manners: Automatic mode
or Manual mode. In automatic mode the controller defines the amount
of power to be applied on the process, based on defined parameters
(SP, PID, etc.).
In the manual mode the user himself defines this amount of power.
The parameter “
” defines the control mode to be adopted.
PID AUTOMATIC MODE
For the Automatic mode, there are two different strategies of control:
PID control and ON/OFF control.
PID control has its action based on a control algorithm that takes into
account the deviation of PV with respect to SP, the rate of change of
PV and the steady state error.
On the other hand, the ON/OFF control (obtained when Pb=0)
operates with 0 % or 100 % of power, when PV deviates from SP.
The determination of the PID parameters (Pb, Ir and Dt) is described
in the item DETERMINATION OF PID PARAMETERS of this manual.
Comentarios a estos manuales